Rated temperature:70
Rated voltage:300/500v
Reference standard:BS6004
Bare stranded or solid copper conductor
Circuit protective conductor is centrally placed between cores in same plane
Flame retardant colour-coded PVC insulation
Flame retardant PVC jacket
Domestic wiring cable for the surface wiring of sockets and lighting where fire, smoke emission and toxic fumes create a potential threat to life and equipment. Can be installed in fixed installations in dry or damp premises clipped to surface, on trays or in free air where mechanical damage would not be an issue. Suitable for laying in conduit or trunking where mechanical protection is required.
Standards:
BS7211
EN 50268
BS EN 50267-2-1
EN 50267
EN 50265
IEC 60332
Conductor: Plain copper conductors to BS EN 60228:2005 (previously BS6360)
Class 1 solid: 1.5mm² and 2.5mm²
Class 2 stranded: 4.0mm², 6.0mm² and 10.0mm²
Class 2 stranded compacted: 16.0mm² Circuit Protection Conductor
(Earth):
Class 1 solid plain copper conductor: 1.0mm², 1.5mm², 2.5mm², 4mm² and 6mm²
Class 2 stranded plain copper conductor: 10mm² and 16mm²
Insulation: XLPE (Cross-linked Polyethylene)
Sheath: LSZH (Low Smoke Zero Halogen)
Sheath Colour: White
Voltage Rating: 300/500V
Temperature Rating: Operating Temperature: -25°C to 90°C Note: Where a conductor operates at a temperature exceeding 70°C it shall be ascertained that the equipment connected to the conductor is suitable for the conductor operating temperature (see regulation 512-02 of BS7671, the 16th Edition of IEE Wiring Regulations)
Conductors: | Plain annealed copper |
Insulation: | PVC (Polyvinyl-Chloride) |
Core identification: | Single core , 2 core, 3 core |
Sheath/Jacket: | PVC (Polyvinyl-Chloride) |
Voltage: | 300/500v |
Operating temperature: | Maximum 70°C, minimum bending 0°C |
Standard: | BS6004 Electric cables. |
Applications: | domestic wiring and lighting systems |
| |
Minimum Bending Radius: 15 x overall diameter Core Identification:
2 Cores: Blue, Brown + Plain
3 Cores: Brown, Black, Grey + Plain
Dimensional Data
Size (sq.mm) | Class Of Conductor | Diameter Over Conductor (mm) | RT Of Insulation (mm) | Diameter Over Core (mm) | Size ECC Conductor (sq.mm) | Diameter Over Laid Up Cores (mm) | Nominal Overall Diameter (mm) | Weight (kg/km) |
1.0 | 1 | 1.13 | 0.6 | 2.3 | 1.0 | 2.3 x 5.8 | 4.1 x 7.6 | 70 |
1.5 | 1 | 1.38 | 0.7 | 2.8 | 1.0 | 2.8 x 6.8 | 4.6 x 8.6 85 | 85 |
1.5 | 2 | 1.59 | 0.7 | 3.0 | 1.0 | 3.0 x 7.2 | 4.8x 9.0 | 90 |
2.5 | 1 | 1.78 | 0.8 | 3.4 | 1.5 | 3.4 x 8.2 | 5.4 x 10.2 | 120 |
2.5 | 2 | 2.01 | 0.8 | 3.7 | 1.5 | 3.7 x 8.9 | 5.7 x 10.9 | 125 |
4 | 2 | 2.55 | 0.8 | 4.2 | 1.5 | 4.2 x 9.8 | 6.2 x 11.8 | 175 |
6 | 2 | 3.12 | 0.8 | 4.7 | 2.5 | 4.7 x 11.2 | 6.9 x 13.4 | 240 |
10 | 2 | 4.05 | 1.0 | 6.1 | 4.0 | 6.1 x 14.8 | 8.5 x 17.2 | 390 |
16 | 2 | 4.80 | 1.0 | 6.8 | 6.0 | 6.8 x 16.8 | 9.4 x 19.4 | 560 |